Cookies on the OMEGA websites We use cookies on this website, these cookies are essential for the website to work correctly.If you continue without changing your settings, we'll assume that you are happy to receive all cookies on this website.To find out more information about these cookies please click here.
The DRSL-DC1 isolated repeater
provides a competitive choice in
terms of both price and technology
for galvanic isolation of current
signals to SCADA systems or PLC
equipment. The unit provides isolation
and 1:1 conversion of standard
current signals.
The unit offers isolation between
input, output and supply. Provides
surge suppression and protects
control systems from transients and
noise. The DRSL-DC1 also eliminates
ground loops and can be used for
measuring floating signals. Low
power consumption facilitates DIN rail
mounting without the need for any air
gap. Measurement ranges are factory
calibrated. The unit operates over a
wide temperature range from
-25 to 70°C (-13 to 158°F).
SPECIFICATIONS CURRENT INPUT Measurement Range: 0 to 20.5 mA Functional Range: 0 to 23 mA Input Voltage Drop: <1.5 Vdc
CURRENT OUTPUT Signal Range: 0 to 20.5 mA (span) Load: 23 mA/600 Ω max Load Stability: ≤0.01% of span/ 100 Ω (span = 0 to 20 mA) Current Limit: ≤28 mA
GENERAL Supply Voltage (via Power Rail or Connectors): 16.8 to 31.2 Vdc Power Consumption: 0.8 W max Internal Consumption: 0.4 W typical/0.65 W max Isolation: Input/output/supply Isolation Voltage (Test): 2.5 kVac Isolation Voltage (Working): 300 Vac MTBF: >284 years, according to IEC 61709 (SN29500) Signal/Noise Ratio: >60 dB Response Time (0 to 90%, 100 to 10%): <7 ms Accuracy: <±0.05 % of span Temperature Coefficient: <±0.01% of span/°C EMC Immunity Influence: <±0.5% of span Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span
ENVIRONMENTAL Operating Temperature: -25 to 70°C (-13 to 158°F) Storage Temperature: -40 to 85°C (-40 to 185°F) Calibration Temperature: 20 to 28°C (68 to 82°F) Relative Humidity: 0 to 95% RH non-condensing Protection Degree: IP20 Installation Area: Pollution degree 2 and measurement/overvoltage category II
MECHANICAL Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5") Weight: 70 g (0.15 lb) approx DIN Rail Type: DIN EN 60715 - 35 mm Wire Size: 0.13 x 2.5 mm2/AWG 26 to 12 stranded wire Screw Terminal Torque: 0.5 Nm