£92.66 TX13
Description
The TX13 in-head mounting thermocouple transmitter converts a thermocouple input over a configured range to a standard industrial (4 to 20 mA) transmission signal. A simple push button operation allows the user to select thermocouple type, burnout direction, select fixed ranges and trim 4 and 20 mA points. The in-head transmitter incorporates the latest digital technology to ensure accurate drift-free performance.
|
Isolation: Tested to 250 Vdc Sensor Burnout: Either up or down scale output Cold Junction: Range: -40 to 85°C Accuracy: ±0.5°C Tracking: ±0.05°C/°C Stability: Offset: 0.1°C/°C Span: 0.05°C/°C Output Type: 2 wire, 4 to 20 mA sink Output Connection: Screw terminal Maximum Output: 21.5 mA (in high burnout condition) Minimum Output: 3.8 mA (in low burnout condition) Accuracy: (mA out/2000) or 5 uA (whichever is the greater) Loop Voltage Effect: 0.2 uA/V Thermal Drift (from 20°C): ±1 uA/°C typical; ±1.5 uA max Maximum Output Load: [(Vsupply-10)/20]KΩ (Example: 700Ω @ 24V) |
||||||||||||||||||||||
Environmental Ambient Operating Range: -40 to 85°C Ambient Storage Temperature: -50 to 90°C Ambient Humidity Range: 10 to 90% RH non condensing Physical Dimensions: 43 mm Dia; 21 mm H Weight: 31 g (encapsulated) |
Update Time: 500 mS Response Time: 1 second to 90% of final value Start Up Time: Typically 5 seconds from power up Warm-Up Time: 1 minute to full accuracy Power Supply: 10 to 30 Vdc |