£179.50 TXDIN1700
Description
The TXDIN1700 is a universal DIN rail mounted signal conditioner. It has been designed to accept most common process and temperature sensor inputs and provide the user with either a current or voltage output signal plus dual relays with a 0 to 250 sec delay function.
Input Type |
Scale / Rate |
Analogue Output |
Relay Outputs |
User Trim Options |
RTD Pt100 .00385 (IEC) Pt100 .00391 (IPTS-68) Pt100 .00392 (IPTS-68) Pt100 .00393 (ITS-90) Ni100 .00618 (DIN) Ni120 .00672 (Nickel A) Cu100 .00427 Cu53 |
|
Current (4 to 20) mA Preset (0 to 20) mA Preset User Programmable Range
Voltage
Fault Condition Output damping rise Output damping fall |
Set-point
High Al
On Delay |
2. Trim 3. Pushbutton Configuration |
T/C K, J, E, N, T, R, S, L, U, B, C(W5), D(W3), G(W) |
||||
Slide Wire > 1KΩ |
Process Variable Scaling Update Rate |
|||
Current (mA) ± 30 mA (4 to 20) mA Capability |
||||
Voltage ± 50 mV ± 200mV ± 1V ± 10V |
||||
Tag ID. |
Up to 15 Characters can be used |
Specifications
Temperature Inputs
INPUT |
RANGE |
ACCURACY |
STABILITY WITH TEMPERATURE |
Thermocouples |
|||
K |
(-200 to 1370) °C (-320 to 2498) °F |
1 Reading / Second ± 0.5 °C + (0.1 % of FSR)
4 Readings / Second ± 1.0 °C + (0.1 % of FSR)
10 Readings / Second ± 2.0 °C + (0.1 % of FSR) |
±0.05 % FSR/°C |
J |
(-200 to 1200) °C (-320 to 2190) °F |
||
E |
(-200 to 1000) °C (-320 to 1832) °F |
||
N |
(-180 to 1300) °C (-292 to 2372) °F |
±0.08 % FSR/°C |
|
T |
(-200 to 400) °C (-320 to 750) °F |
±0.15 % FSR/°C |
|
R *1*2 |
(-10 to 1760) °C (-148 to 3200) °F |
±0.10 % FSR/°C |
|
S *1*2 |
|||
L |
(-100 to 600) °C (-148 to 1100) °F |
±0.08 % FSR/°C |
|
B *1*2 |
(0 to 1600) °C (32 to 3000) °F |
±0.10 % FSR/°C |
|
U |
(0 to 600) °C (32 to 1100) °F |
±0.08 % FSR/°C |
|
C(W5) *2 |
(0 to 2300) °C (32 to 4200) °F |
±0.05 % FSR/°C |
|
D(W3) *2 |
|||
G(W) *2 |
|||
RTD |
|||
Pt100.00385 (IEC) |
(-200 to 850) °C (-320 to 1560) °F |
1 Reading / Second ± 0.15 °C + (0.05 % of FSR)
4 Readings / Second ± 0.5 °C + (0.1 % of FSR)
10 Readings / Second ± 1.0 °C + (0.1 % of FSR) |
±0.015 % FSR / °C *3 |
Pt100 .00391 (IPTS-68) |
(-200 to 630) °C (-320 to 1160) °F |
||
Pt100 .00392 (IPTS-68) |
|||
Pt100 .00393 (ITS-90) |
(-200 to 960) °C (-320 to 1760) °F |
||
Ni 100 .00618 (DIN) |
(-60 to 180) °C (-76 to 320) °F |
||
Ni120 .00672 (Nickel A) |
(-80 to 260) °C (-112 to 460) °F |
||
Cu100 .00427 |
|||
Cu 53 (GOST) |
(-50 to 180) °C (-58 to 320) °F |
Key. FSR = Full Scale range
*1 only over the range (800 to 1600) °C, *2 cold junction tracking range (0 to 70) °C, *3 Ambient (-10 to 50) °C
Impedance (Thermocouple): 1 MΩ
Open Circuit sensor bias: 0.2 uA
Cold junction range: -20 to +70°C
Cold Junction Accuracy: ± 0.5°C
Cold Junction Tracking: ± 0.05°C
RTD Connection: 2 or 3 wire
RTD Lead Resistance: 20 Ω Max
RTD Lead effect: 0.015 °C / Ω
RTD Excitation Current: < 1 mA
Update Rate (Resolution): 1 readings / second (16 Bits); 4 Readings / Second (14 Bits); 10 readings / Second (12 Bits)
Galvanic Isolation: 500 V to output: 3750 V to supply and Relays
Indication (State LED): Green Flashing = OK, Green Solid = input/output error configuration indication refer to manual.
Process Inputs
INPUT |
RANGE |
ACCURACY @ 20°C |
STABILITY WITH TEMPERATURE |
50 mV |
± 50 mV (Max ± 75 mV) |
1 Reading / Second ±0.04% + (0.1% of FSR)
4 Readings / Second ± 0.1 % + (0.1 % of FSR)
10 Readings / Second ± 0.2 % + (0.1 % of FSR) |
± 0.04 % FSR/ °C |
200 mV |
±200 mV (Max ± 230 mV) |
||
1 V |
± 1 V (Max ± 1.3 V ) |
||
10 V |
± 10 V (Max ± 11 V) |
||
mA |
± 25 mA (Max ±30 mA) |
||
Slide Wire |
(0 to 100) % (1 to 1000) KΩ pot |
± 0.05 % / °C |
|
Ohms |
(20 to 400) Ω Max (0 to 480) Ω |
± 0.025 % FSR / °C |
Voltage Input Impedance: 1 MΩ
Current Input Impedance: 20 Ω
Slide Wire Input Range: 1 KΩ to 1000 KΩ Pot
Resistance Connection: 2 or 3 Wire
Galvanic Isolation: 500 V to output: 3750 V to supply and Relays
Update Rate (Resolution): 1 readings / second (16 Bits); 4 Readings / Second (14 Bits); 10 readings / Second (12 Bits)
Current Output
Ranges: 4 to 20 mA; 0 to 20 mA; User (between 0 and 24 mA; min span 0.5)
Fault Signal: Up: 22.5 mA, Down: 3.8 mA, User: 0 to 25 mA
Type: Two wire current sink; or two wire current source
Supply in sink mode: (11 to 30) V dc, 24 V nominal
Max loop load: Sink mode loop load of 600 Ω @ 24 V; Source mode 550 Ω
Response time: < 500 ms to reach 95 % of final value; Start up time < 3 s
Calibration Accuracy: ± 5 uA
Loop Effects: Loop ripple 0.03 % of FSR;
Supply sensitivity: Supply ripple rejection < ± 5 uA error @ 1 V rms 50 Hz ripple
Protection: Reverse connection and over-voltage protection. Max over voltage current 100 mA.
Current Output Damping: Programmable rise and fall (0 to 250) seconds, for a (0 to 20) mA swing.
Stability: ± 5 uA / °C
Voltage Output
Ranges: 0 to 10 V, User (0 to 12 V, span 0.5 V)
Fault Signal: Up: 11.5 V, Down: 0V, User: 0 to 13 V
Type: Voltage generated across 500 Ω resistor
Min Load: 10 KΩ User Configurable correction for Load.
Response time: < 500 ms to reach 95 % of final value; Start up time < 3 s
Calibration Accuracy: ± 5 mV
Galvanic Isolation: 500 V (48 Vdc working I/P to O/P), 3750 V to supply and Relays
User Trim: Push button user adjust at both zero and span
Voltage Output Damping: Programmable rise and fall (0 to 250) seconds, for a (0 to 10) V swing.
Stability: ± 1mV / °C
Relay Outputs
Type: Dual Form C relay contacts
Contact rating: (240 V ac rms @ 1A; 30 V dc @ 1 A) Resistive Load
Relay Type: Individual relays 1 & 2 high or low level, full range set-point plus adjustable Hysteresis
Ranges: Set-point programmed on units, covering full range of input. Hysteresis Set in units.
Isolation: To any other port 3750 V
Delay: Programmable on / off delay (0 to 250) seconds for each relay.
Power Supply
Range: (20 to 240) V dc, (20 to 240) V ac 50/60 Hz
Power: 3 W max
Protection: Internal fuse, Over Voltage
Galvanic Isolation: Supply to any port 3750 V
General
Ambient Operating: (-20 to 70) °C (10 to 95) % RH non-condensing.
Storage Temp.: (-40 to 85) °C
Approvals: CE tested to BS EN 61326; BS EN 61010_1
Dimensions: 120 deep, 106 high, 22.5 mm wide